Rotable Parts Exchange serves as a comprehensive source for military products, aerospace equipment, and Alarm Gas Automatic items. You have expressed particular interest in part number CM-21A, a 3M Company component we offer that is presented with the NSN 6665-01-530-2725 for straightforward identification and procurement. By completing and submitting the Request for Quote form provided on this page, you can obtain pricing details on this NSN part for your comparisons. Once our staff members receive and review your submitted information, a dedicated account manager will directly contact you with a response within 15 minutes or less.
Note : We Will Not Share Your Information To Any Third Parties.
We strive to streamline the purchasing process and simplify it as much as possible, which includes providing detailed listings for all components to help customers pinpoint their exact needs. For instance, part number CM-21A is manufactured by 3M Company under the CAGE Code 76381. Additionally, by using the initial digits of the NSN 6665-01-530-2725, you can discover that this component is associated with the FSC 6665 Hazard Detecting Instruments And Apparatus. If you have any specific questions about our database, you may always give us a call or email, as we would be delighted to assist you however we can. Otherwise, we encourage you to secure a quote for part number CM-21A at your earliest convenience.
MRC | Criteria | Characteristic |
---|---|---|
APGF | DESIGN TYPE | NONTRIPOD MOUNTING |
AFJK | III CUBIC MEASURE | 38.250 CUBIC INCHES |
SUPP | III SUPPLEMENTARY FEATURES | DIMENTIONS ARE 4.5 X 4 X 2.125 INCHES. ITEM SHOULD BE MOUNTED 4 TO 5 FEET ABOVE FLOOR LEVEL. |
FEAT | SPECIAL FEATURES | CM-21A ACTIVATES FAN RELAY AT 35 PPM OF CO AVERAGED OVER 5 MINUTES. (25 PPM IS SELECTABLE) ALARM RELAY WILL BE ACTIVATED AT 100 PPM OF CO AFTER 30 MINTUTES OR 200 PPM AFTER 10 MINUTES. 5 AMP SPDT FAN RELAY CONTROLS STARTERS OF EXHAUST FANS. A 0.5 AMP N.O. ALARM RELAY CONNECTS TO WARNING DEVICES OR CONTROL PANELS. |
BRQN | MEDIA DETECTED | CARBON MONOXIDE |
CXCY | III PART NAME ASSIGNED BY CONTROLLING AGENCY | CARBON MONOXIDE DETECTOR AND CONTROLLER |
ALBY | USAGE DESIGN | INDUSTRIAL |
ALXZ | SPECIFIC USAGE DESIGN | DESIGNED FOR CO DETECTION AND AUTOMATED EXHAUST FAN CONTROL IN AUTOMOTIVE MAINTENANCE FACILITES, ENCLOSED PARKING GARAGES, WAREHOUSES WITH FORKLIFTS, ETC. |
AMKD | INDICATOR TYPE | RED LIGHT AND HORN |
If You’re Ever Looking for NSN parts Or Have an Aircraft On Ground Situation, Don’t forget That We offer Competitive Pricing and Guaranteed On-Time Delivery.